CÔNG TẮC ÁP SUẤT 2 TIẾP ĐIỂM SYSTEM SENSOR EPS10-2
The EPS10-1 has a single SPDT switch while the EPS10-2 model contains two SPDT switches. The EPS10 Series features field adjustable pressure sensitivity to provide an alarm response between 4 and 20 psi. It is factory set to respond at 4 – 8 psi on rising or falling pressure. The pressure adjustment wheel requires no special tools and does not affect switch synchronization on the EPS10-2. The EPS10 Series switches are NEMA 4 rated
Thông số kỷ thuật
Mã sản phẩm : EPS10-2
Thương hiệu : SYSTEM SENSOR
Xuất xứ : Trung Quốc
Adjustment Pressure Range : 4-20 PSI
Contact Ratings : Two sets SPDT (Form C); 10.0A, 1/2 HP @ 125/250VAC; 2.5A @ 6/12/24VDC
Differential : Approx. 3 PSI throughout range
Enclosure Rating : UL NEMA 4
Factory Setting : Operates at rising pressure 4-8 PSI
Operating Temperature Range : -40°F to 160°F (-40°C to 71°C)
Overall Dimensions : 5.12"H x 3.325"W x 4.25"L (13cm x 8.4cm x 10.8cm)
Pressure Connection : 1/2" NPT male glass reinforced nylon
Shipping Weight : 1.2 lbs. (.54 kg)
UL Pressure Rating : 250 PSI
Warranty : 3 years
Architectural/Engineering Specifications EPS10-1 (SPDT), EPS10-2 (2/SPDT)
Model shall be an EPS10-1 or EPS10-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type. Switches shall have a maximum service pressure rating of 300 psi and shall be factory adjusted to operate at a pressure of 4 – 8 psi. There shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 6/12/24 VDC. The contractor shall furnish and install, where indicated on the plans, pressure switches according to appropriate NFPA standards. Switches shall be provided with a ½˝ NPT male pressure connection to be connected to the alarm check valve of a “wet” sprinkler system, into the intermediate chamber of a “dry” system, or to a pre-action or deluge valve. They shall be activated by any flow of water equal to or in excess of the discharge from one sprinkler head. Switches shall provide 1 knockout type and 1 open hole for ½˝ conduit fitting attachment and a ground screw provision for electrical grounding. The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings and conduit. The cover shall incorporate tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc. and approved by Factory Mutual.